dc.contributor.authorLópez Chachalo, Alex Julián-
dc.date.accessioned2018-01-11T19:45:29Z-
dc.date.available2018-01-11T19:45:29Z-
dc.date.issued2018-01-11-
dc.identifier.citationLópez Chachalo, A. J. (2018). Evaluación del impacto de ceniza volcánica en la rigidez dieléctrica de aisladores de suspensión en líneas de alto voltaje mediante análisis del factor de pérdida dieléctrica. 135 hojas. Quito : EPN.es_ES
dc.identifier.otherT-IE/4587/CD 8469-
dc.identifier.urihttp://bibdigital.epn.edu.ec/handle/15000/19068-
dc.descriptionEn este proyecto se realizó un análisis experimental de la afectación de la ceniza volcánica sobre los aisladores eléctricos ANSI 52-3, generalmente utilizados en líneas de transmisión de 138 kV y 230 kV. Para ello se utilizaron muestras de ceniza de los volcanes Cotopaxi y Tungurahua. Se determinó los niveles críticos de acumulación de ceniza volcánica sobre la superficie de los aisladores, con los cuales se tendría un alto riesgo de falla. Se planteó también una metodología para desarrollar pruebas experimentales en un laboratorio de alto voltaje, en base a normas y procedimientos para pruebas en aisladores externos con contaminación. Se implementó un sistema de medición y monitoreo de parámetros eléctricos, que juntamente con la metodología propuesta para el desarrollo experimental, permite llegar a obtener los resultados. Finalmente se presentaron los resultados obtenidos de las pruebas experimentales realizadas en el Laboratorio de Alto Voltaje de la Escuela Politécnica Nacional, realizando un análisis de los mismos, y se determinaron las líneas de transmisión que se verían afectadas en distintos escenarios y niveles de contaminación con ceniza volcánica.es_ES
dc.description.abstractIn this project, an experimental analysis of the involvement of volcanic ash on the ANSI 52-3 electrical insulators, generally used in 138 kV and 230 kV transmission lines, was carried out. For this purpose, ash samples from the Cotopaxi and Tungurahua volcanoes were used. The critical levels of accumulation of volcanic ash on the surface of the insulators were determined, with which there would be a high risk of failure. A methodology was also proposed to develop experimental tests in a high voltage laboratory, based on standards and procedures for tests on external insulators with contamination. A system of measurement and monitoring of electrical parameters was implemented, which together with the methodology proposed for the experimental development, allows us to obtain the results. Finally, the results obtained from the experimental tests carried out in the High Voltage Laboratory of the National Polytechnic School were presented, performing an analysis of them, and the transmission lines that would be affected in different scenarios and levels of volcanic ash contamination, were determined.es_ES
dc.description.sponsorshipValencia Arcos, Fausto Ramiro, directores_ES
dc.language.isospaes_ES
dc.publisherQuito, 2018.es_ES
dc.rightsopenAccesses_ES
dc.rights.urihttps://creativecommons.org/licenses/by-nc-nd/4.0/-
dc.subjectAISLADORES ELÉCTRICOSes_ES
dc.subjectALTO VOLTAJEes_ES
dc.titleEvaluación del impacto de ceniza volcánica en la rigidez dieléctrica de aisladores de suspensión en líneas de alto voltaje mediante análisis del factor de pérdida dieléctricaes_ES
dc.typebachelorThesises_ES
Aparece en las colecciones:Tesis Ingeniería Eléctrica (IE)