dc.identifier.citationMosquera Morales, A. E., & Romero Cando, D. C. (2018). Evaluación de la eficiencia y optimización de los procesos de potabilización de la planta de tratamiento de agua potable de Conocoto, parroquia rural del DMQ. 300 hojas. Quito : EPN.es_ES
dc.identifier.otherT-IC/0858/CD 8695-
dc.identifier.urihttp://bibdigital.epn.edu.ec/handle/15000/19325-
dc.descriptionBasado en el Manual III del CEPIS, se evaluó el funcionamiento hidráulico de la Planta Potabilizadora “Conocoto”, diseñada para remover turbiedad. Se analizaron estadísticamente datos de turbiedad, color y C. fecales, del último año de operación de la planta (2016), evidenciando una eficiencia de remoción de turbiedad del 96.3% en verano y 88.4 %, en invierno. Las condiciones hidráulicas del floculador y los sedimentadores, se evaluaron mediante el ensayo de trazadores utilizando NaCl, resultando tiempos de retención y cortocircuitos en menor porcentaje, predominando el flujo pistón en los sedimentadores. Los filtros fueron evaluados bajo los parámetros: características del sistema del lavado y del agua filtrada, estado del medio filtrante; evidenciando la pérdida del lecho filtrante y la valoración del tiempo de lavado. De los ensayos de tratabilidad, se determinó una concentración y dosis óptimas de Al2(SO4)3 del 1% y 85 mg/l, respectivamente, dosis óptima de ayudante de floculación =0.25 mg/l, pH =7, gradiente de floculación de 20 s-1 y con tiempo óptimo de sedimentación de 20 min. En la desinfección se determinó una dosis óptima de 1.45 mg/l Cl2 y en la distribución se determina para San Juan y Santa Mónica concentraciones de 0.5 mg/l y 0.3 mg/l, respectivamente.es_ES
dc.description.abstractBased in the Manual III proposed by the CEPIS, the Conocoto water treatment plant is evaluated the hydraulic functioning, designed to removed turbidity. The data of the last year of operation were analyzed, in terms of turbidity, color and fecal coliform parameter, showed a removal efficiency of 96.339% in summer and 88.439% in winter. The testing of tracer was accomplished using NaCl, for evaluate the hydraulic conditions of the flocculation and sedimentation units resulting the times of retention and short circuits lows, predominantly the piston flow in the settlers. The filters were evaluated under the parameters: characteristic of washing system and filtered water, state of the filtering medium, showed the lost filter bed and washing time evaluation. Treatability tests were accomplished, resulting in an optimum concentration of 1% aluminum sulfate; the optimal dose= 85 mg/l; pH = 7 and gradient of 20 s-1 with optimal sedimentation time of 20 min. The evaluation of disinfection we could determinate an optimal doses of 1.5 mg/l Cl2, and in the distribution, we determinate for San Juan and Santa Monica a concentration of 0.5 mg/l and 0.3 mg/l Cl2, respectively.es_ES
dc.description.sponsorshipBalarezo Aguilar, Ana Lucía, directores_ES
dc.language.isospaes_ES
dc.publisherQuito, 2018.es_ES
dc.rightsopenAccesses_ES
dc.subjectCALIDAD DEL AGUAes_ES
dc.subjectHIDRÁULICAes_ES
dc.subjectPOTABILIZACIÓNes_ES
dc.titleEvaluación de la eficiencia y optimización de los procesos de potabilización de la planta de tratamiento de agua potable de Conocoto, parroquia rural del DMQes_ES
dc.typebachelorThesises_ES
Aparece en las colecciones:Tesis Ingenieria Civil y Ambiental (ICA)